NFRC Ratings and the Assumptions Behind Them
NFRC Ratings and the Assumptions Behind Them: what each label number is measured under, and when it stops describing your building.
NFRC Ratings and the Assumptions Behind Them: What Gets Rated
A label carries five ratings, produced by different procedures under different modelled conditions. They are not five views of the same test.
| Rating | Procedure | Determined under | The assumption it carries |
|---|---|---|---|
| U-factor | ANSI/NFRC 100 | A winter night: no sun, a large indoor to outdoor temperature difference, a steady wind | Heat flow driven by temperature alone |
| SHGC | ANSI/NFRC 200 | A summer day with the sun striking the glazing head on | Solar energy arriving at normal incidence |
| VT | ANSI/NFRC 200 | The same summer condition as SHGC | Light measured through the whole product, frame included |
| Air leakage | A separate NFRC procedure | A pressure difference across the product | The product as manufactured, not as installed |
| Condensation resistance | A separate NFRC procedure | Modelled indoor humidity and temperature conditions | A comparative index, not a prediction for your building |
Every one of those conditions is a decision someone had to make so that two products could be compared at all. Knowing which decision sits behind which number is most of what separates careful specification from quoting a sticker.
Assumption One: A Winter Night With No Sun
ANSI/NFRC 100 fixes the conditions under which every U-factor is determined.
- Interior ambient temperature of 21.0°C (69.8°F)
- Exterior ambient temperature of −18.0°C (−0.4°F)
- Wind speed of 5.5 m/s (12.3 mph)
- Solar irradiance of 0 W/m² (0 Btu/h·ft²)
Read that list again and notice what is missing. There is no sun. U-factor is a night-time winter number by construction, which is exactly why it describes conduction and says nothing about solar gain. A product can hold a very low U-factor and still overheat a room in July, and nothing about the rating was ever claiming otherwise.
Notice also the size of the temperature difference. Thirty-nine degrees Celsius across the assembly is a severe winter night in most of the country and no night at all in some of it. The standard itself is explicit that the values “are determined at a fixed set of environmental conditions” and, because of that, may not suit direct estimates of seasonal energy performance.
So U-factor answers one question precisely: under identical severe winter conditions, which of these products conducts heat more slowly? That is a genuinely useful question. It is just not the same question as how much energy the building will use.
Assumption Two: A Summer Day, Sun Straight On
ANSI/NFRC 200 fixes a different set of conditions for solar heat gain coefficient and visible transmittance.
- Outdoor air temperature of 32°C (90°F)
- Indoor air temperature of 24°C (75°F)
- Wind speed of 2.75 m/s (6.15 mph)
- Direct solar irradiance of 783 W/m² (248 Btu/h·ft²)
The critical assumption is not in that list. It is the angle. The procedure determines these values at normal incidence, with the sun striking the glazing straight on, and the standard says so plainly: the values may not be suitable for peak solar gains at other incident angles, for diffuse radiation, or for seasonal energy performance.
That single sentence explains a great deal of field experience. Afternoon sun on a west elevation arrives at a low, oblique angle for hours, and glazing behaves differently at those angles than it does at the one the rating used. An overcast sky delivers diffuse light, which the rating also does not represent. Neither case makes the SHGC wrong. Both make it incomplete as a prediction.
The practical consequence: SHGC is a comparison tool for ranking products, and a starting input for modelling, not a forecast of what a given opening will admit at four in the afternoon in August.
Our products
Six film families, one for every kind of glass
To change the solar numbers on existing glass, start with Architectural Solar Control. Every family has its own page with the full range.
- Clarity IR Max
- Nano Ceramic
- Climate IQ 50
- Skyline
- Harmony DR
- Soft Tone
- Eco Silver 20
- X-Clear 70
- X-Eco Silver 15
- X-Hybrid DR 15
- Safety 4 Clear
- Security 8 Clear
- Security 8 Silver
- Security 14 Clear
- X-Safety 7
- AG 6 Clear
- Frost
- White Out
- Black Out
- Poly Layers
- V6 Comfort BLK
- V10 Ceramic IR BLK
- V16 Ceramic IR MAX
- V6 Core
- V10 Reactive
- V16 Velocity
Assumption Three: One Standard Size
A certified rating does not belong to a product in the abstract. It belongs to that product at a defined size.
Ratings are determined at the model sizes set out in NFRC 100. A few of them:
- Fixed window: 1200 mm by 1500 mm (47 in. by 59 in.)
- Single casement: 600 mm by 1500 mm (24 in. by 59 in.)
- Skylight or roof window: 1200 mm by 1200 mm (47 in. by 47 in.)
- Sliding patio door with frame: 2000 mm by 2000 mm (79 in. by 79 in.)
Size matters because the frame and the glass perform differently, and changing the dimensions changes the proportion of each. A large fixed light is mostly glass, so its behaviour tends toward the glass values. A small unit of the same product carries proportionally more frame and edge, and shifts away from them.
NFRC 200 permits calculation at non-standard sizes “for purposes other than certification”, which is a precise way of saying that a certified rating belongs to the model size and that anything else is a separate calculation. If a project uses units far from the model size, the certified number is still the right basis for comparing products and the wrong basis for assuming performance at the real dimensions.
Assumption Four: The Whole Product, Not the Glass
NFRC rates the entire unit, glass and frame and spacer together, rather than the centre of the glass.
That decision was deliberate, and it was the right one, because most heat loss happens at the edges and a centre-of-glass figure hides it. It also has consequences that catch people out when they compare a glass data sheet with a window label:
- Whole-unit U-factors are typically higher than centre-of-glass values.
- Whole-unit visible transmittance is lower, because the frame blocks light at the edges.
- Framing can pull SHGC below the figure quoted for the glass alone.
None of those differences mean anyone is being dishonest. They mean the two numbers were drawn around different boundaries. A centre-of-glass value describes the glazing; a whole-product value describes the thing that gets installed.
One more boundary is worth stating out loud: NFRC ratings reflect the product as manufactured, not as installed. A superb assembly fitted badly performs badly, and no label can see that.
What the Ratings Deliberately Exclude
A standard is as useful for what it rules out as for what it measures, and NFRC is unusually direct about its own limits.
Seasonal and annual energy use. NFRC 100 states that its U-factors may not be suitable for direct estimates of seasonal energy performance. Modelling does that job, using the ratings as inputs.
Performance over time. NFRC 100 says the procedure does not address long-term changes in energy performance. Seal failure, coating degradation and the ordinary ageing of an assembly sit outside it.
Water tightness and structural capacity. Named directly in NFRC 100 as outside its scope, and covered by other standards entirely.
Installation. The rating describes manufacturing. Everything that happens at the opening is somebody else’s responsibility and somebody else’s test.
Glare, comfort and fading. No single rating captures any of them. They depend on sun angle, interior contrast, materials and exposure time.
Reading a Label With the Assumptions in Mind
Six questions cover most of the ways a comparison goes wrong. They are worth asking even when the numbers come from a source you trust, because the mismatch is usually accidental.
| When you see | Ask | Because |
|---|---|---|
| A U-factor | Whole product or centre of glass? | The whole-product figure is usually the higher of the two |
| An SHGC | At what size, and against what frame? | Frame proportion changes with the model size |
| A VT | Does it include the frame? | Whole-product VT is lower than the glass value |
| Two products side by side | Same procedure, same size, same basis? | Only then is the comparison the one it appears to be |
| A number used as a prediction | Prediction of what, under which weather? | The ratings are fixed-condition comparisons, not forecasts |
| A film or glass data sheet | On which base glass was this generated? | Film performance is always published against a stated glass |
None of these questions is adversarial. Any competent manufacturer or dealer can answer all six in a sentence each, and the answers are what make two numbers genuinely comparable.
Keep reading
More on building envelope and energy
Why Two Honest Numbers Can Still Mislead
Almost no misleading comparison involves a wrong number. It involves two right numbers resting on different assumptions.
- Different boundaries. A centre-of-glass U-factor against a whole-product one. Both correct, not comparable.
- Different sizes. A certified rating at the model size against a calculated value at the project size.
- Different questions. A winter U-factor quoted in an argument about summer overheating, where SHGC is the number that matters.
- Different angles. A normal-incidence SHGC used to reason about a west elevation at five in the afternoon.
- Different documents. A manufacturer’s own figure set beside a third-party certified one, with no note of which is which.
The fix is dull and effective: establish the basis before comparing the values. Once both sides of a comparison are on the same footing, most disagreements about glazing performance turn out to be disagreements about something else, usually priorities.
What Happens When Film Changes the Glazing After the Rating
A certified rating describes an assembly at a moment in time. Applying film to existing glass creates a new assembly.
Three things follow from that, and all three come back to the assumptions above.
The rating on the window no longer describes the window
Once film is on the glass, the assembly is not the one that was certified. Its solar behaviour has changed, and the label in the corner of the frame now describes the product as it left the factory rather than as it stands today.
Film ratings carry the same assumptions
Films can carry NFRC solar heat gain coefficient and visible transmittance ratings, and certified ones appear in the NFRC Certified Products Directory. Those figures inherit the conditions in NFRC 200, normal incidence included, and they are published against a stated base glass. The same film on a different glazing is a different assembly with different numbers.
What film does not change
Conduction, largely. efficientwindows.org notes that film “does not provide substantial insulating benefits” and points to storm windows where insulation is the objective. It also warns that because film absorbs solar energy it can raise glass temperature and “may cause thermal stress on the glass or insulated glazing seals”, and advises checking whether application affects the existing window warranty. On a coated or insulated unit, that check is part of the specification, not an afterthought.
How to Use the Ratings Well
The assumptions are not a reason to distrust the numbers. They are a reason to use each number for the job it was designed to do.
Use certified ratings for what they are built for: ranking products against each other on an identical basis. That is a real and valuable job, and nothing else does it as well.
Use modelling for the questions the ratings exclude. Seasonal energy use, orientation, shading, occupancy and real weather belong in a model that takes the ratings as inputs.
Use a survey for anything involving existing glass. The construction actually on site decides which film can be specified and what the resulting assembly will do, and no published table can substitute for knowing what is in the frame.
Know the Question Before You Trust the Answer
NFRC ratings are among the more honest numbers in construction, precisely because the standards state their own limits so clearly.
Every rating is an answer to a question someone had to phrase precisely before it could be measured. Knowing the phrasing tells you when the answer applies and when it has been stretched past its evidence.
In practice that comes down to three habits: check the basis before comparing two figures, keep fixed-condition ratings separate from predictions about a real building, and survey existing glass rather than assuming it.
ProLayers supplies architectural and automotive window film through its dealer network, with published performance data for each product. A dealer can confirm the glazing on site and match a film to the performance the project needs, on the same basis the numbers were written.
Suggested product: Clarity IR Max 75. UV protection with almost no change in appearance. View the product
FAQ
Frequently asked questions
Six quick answers about NFRC ratings and what sits behind them.
Still have a question? Ask usWhat conditions is a U-factor measured under?
ANSI/NFRC 100 fixes them: 21.0°C (69.8°F) indoors, −18.0°C (−0.4°F) outdoors, a wind speed of 5.5 m/s (12.3 mph) and zero solar irradiance. It is a winter night-time condition, which is why U-factor describes conduction rather than solar gain.
What conditions produce the SHGC and VT figures?
ANSI/NFRC 200 uses 32°C (90°F) outdoors, 24°C (75°F) indoors, a wind speed of 2.75 m/s (6.15 mph) and direct solar irradiance of 783 W/m² (248 Btu/h·ft²), with the sun at normal incidence.
Can I use NFRC ratings to predict my energy bills?
Not directly. NFRC 100 states that values determined at its fixed conditions may not be suitable for direct estimates of seasonal energy performance, and NFRC 200 says the same about peak solar gains at other angles, diffuse radiation and seasonal performance. The ratings are inputs to that kind of analysis rather than a substitute for it.
Why does the rated size matter?
Because the frame and the glass perform differently and the model size fixes the proportion between them. NFRC 200 allows calculation at non-standard sizes for purposes other than certification, which means a certified number belongs to the model size.
Why is a whole-product number worse than the glass number?
It is not worse, it is wider. The whole-product figure includes the frame, spacer and edges, where more heat moves and where light is blocked, so whole-unit U-factors are typically higher and whole-unit VT lower than centre-of-glass values.
Does the label still apply after window film is installed?
The label describes the product as manufactured. Film changes the glazing, so the solar numbers for the assembly change with it. Films can carry their own NFRC SHGC and VT ratings, published against a stated base glass and determined under the same NFRC 200 conditions.